With the refrigerant system completely evacuated the system can now be opened to allow the refrigerant
charge in the Outdoor unit to be released into the line set
e
erv
ce
a
ves requ
re a
mm an
a 5mm
en wrenc
respect
ve
y to un
o t
e va
ve stems
emove t
e
caps
rom t
e
erv
ce
a
ves
Open the SUCTION line Valve first to prevent any possible oil logging of the Capillary tub
This can occur if the liquid line valve is opened first with the rest of the system in a deep vacuum
Then open the "LIQUID or EXPANDED GAS" line
Unscrew both valve stems until they come to a stop against the valve body, replace the Brass Caps and
then tighten the caps to prevent leaks
Energize the breaker to allow system to be powered
Start Indoor unit, Cooling mode is only allowed when the Outside Ambient Temperature is above 65 DegF to
prevent damage to the compressor
Unit has a 3 minute time delay for the compressor start up operation
Unit is charged with enough R410A refrigerant for a line set of 25ft length
For longer line set lengths additional charge must be WEIGHED in per the following table
30ft 35ft 40ft 45ft
1.5oz 3.0oz 4.5oz 6.0oz
2.5oz 5.0oz 7.5oz 10.0oz
1.5oz 3.0oz 4.5oz 6.0oz
2.5oz 5.0oz 7.5oz 10.0oz
Standard Operation of the unit - Cooling
Indoor Temperature Split 30 DegF
Suction Pressure 115 Psig, approx 37 DegF
Suction Line Temperature 45 DegF
Schraeder connection on the "Liquid" line DOES NOT READ
HEAD PRESSURE - it is an expanded gas pressure
Standard Operation of the unit - Heat Pump
Indoor Temperature Split 30 DegF
High Side Pressure 400 Psig, approx 117 DegF
(Measured at Liquid Line Schraeder)
Discharge (Liquid) Line Temperature 130 DegF
QCIC-09 & 12
QCIC-18 & 24
QCIH-09 & 12
QCIH-18 & 24
Added Charge required for a line set of
Unit
Installation and Maintenance Manual
Unit Start Up
Open Suction Line
Valve First